TSBSC - OPERATING MODE
Overload operation mode Overload operating mode
The Shock Relay does not respond to motor starting current within the preset start time period. The Shock Relay does not respond to motor starting current within the preset start time period. Overload operating mode
The Shock Relay does not respond to excess current (spike) if it does not exceed the preset shock time. The Shock Relay does not respond to excess current (spike) if it does not exceed the preset shock time.
The Shock Relay responds when excess current exceeds the preset shock time. The Shock Relay responds when excess current exceeds the preset shock time.
Motor rotational speed
Shock Relay operation (trip)
Motor rotational speed
Shock Relay operation (trip)
Motor load current
Short period of over current (not want to stop due to spike)
Overload
Motor load current
Short period of over current (not want to stop due to spike)
Time
Start time setting value
Shock time setting value
Shock time setting value Overload Abnormal (Overload) area
When motor starts
Steady area
Motor stops
Time
Start time setting value
Shock time setting value
Shock time setting value
Light load operation (underload detection) mode Abnormal (Overload) area Steady area When motor starts
Motor stops
Once the motor current falls below the preset level, underload is detected and a signal is sent to stop the motor. For under-load detection, the output contact is set to alarm output.* * However, in case of the underload detection, the output contact becomes choice of either alarm output or no action.
The Shock Relay does not respond to short- term current degradation if it does not exceed the preset shock time. The Shock Relay does not respond to short- term current degradation if it does not exceed the preset shock time.
The Shock Relay responds when current degradation continues for longer than the preset shock time. The Shock Relay responds when current degradation continues for longer than the preset shock time.
Shock Relay operation (trip)
Motor load current
Shock Relay operation (trip)
Short period of under current (not want to stop due to spike) Motor load current
Current drop
Short period of under current (not want to stop due to spike)
Time
Start time setting
Shock time starting
Shock time starting Current drop Abnormal (Underload) area
When motor starts
Steady area
Motor stops
Time
Start time setting
Shock time starting
Shock time starting
When motor starts
Steady area
Abnormal (Underload) area
Motor stops
Communication function
Communication Specification
Item
Content
Transmittance standards
RS-485
Max. transmittance distance
1200m (depends on transmittance speed) Half-duplex system; modbus protocol
Transmittance system Transmittance speed
1.2k to 38.4kbps