HOW TO ORDER
The model code listed below is intended to provide an example of how a given Tsubaki Shock Relay is configured. The most important aspect of ordering a Tsubaki Shock Relay is knowing the electric drive motor horsepower, voltage and amperage rating. As seen below, these three attributes are used to select the correct size range. Selecting a given series is a matter of preference based upon the features and benefits of a given Shock Relay series.
How to Order Code: Example Model # TSBSB Series Shock Relay TSB SB 30
Shock Relay
Series
Max Amperage Amperage Range 230 Volt Motor HP* 460 Volt Motor HP*
5
0.5 - 6A
1/8 to 1 HP
1/4 to 3 HP
10
1 - 12A
2 to 3 HP
3 to 5 HP
30
3 - 30A
5 to 7 HP
7 to 15 HP
SB Series: Basic overload protection. Manual reset with fail safe contact
Tsubaki Shock Relay Overload Protection
60
5 - 60A
10 to 15 HP
20 to 30 HP
100
10 - 100A
20 to 25 HP
40 to 60 HP
200
20 - 200A
30 to 50 HP
70 to 120 HP
300
30 - 300A
60 to 100 HP
150 to 175 HP
* The motor horsepower ranges are approximates; best option is to select based on actual current readings.
The above example for the TSBSB series Shock Relay is used to illustrate the various models within one Shock Relay series and How to Order a Shock Relay for your application. TSB: There are two families within Tsubaki’s line of electronic protection devices. The Shock Relay series begins with TSB. The Shock Monitor series begins with TSM. SB: The SB-series is one of five types of Shock Relays, each having slightly different features and focusing on different types of applications. While there is overlap between the Shock Relay series, the combinations of features such as ease of set-up, type of display, and communication options will make one Shock Relay series more desirable than another. See the preceding page for a delineation of the various Shock Relay series. 30: The numerical sizing of a Shock Relay series. The TSBSB series is available in seven sizes and for this series, the number relates to the max amperage rating for that Shock Relay. While all Shock Relays can be adjusted over a wide range of amperages, here are a few suggestions that will aid with selection: • Select the Shock Relay based on actual running amperage There is a tendency to oversize the electric motor for the application. For example, the motor nameplate may say 6 amps but measurement shows the application only uses 3 amps. Select the Shock Relay based on the 3-amp reading.
www. ustsubaki .com