U.S. TSUBAKI SHOCK RELAY
SPECIFICATIONS
SPECIFICATIONS*
FEATURES
TSB151
TSB152
Motor Amps
0.25 - 16 amps
17 - 400 amps
Load Current Range
30 - 130%
30 - 130%
Start Time Setting Range Shock Time Setting Range Input Voltage for Operation Allow. Input Voltage Fluctuation Input Current from C.T. Secondary Meter Fine Tuning Adjustment
0.2 - 20 sec. 0.2 - 3 sec.
0.2 - 20 sec. 0.2 - 3 sec.
115/230 Volt 50/60 Hz
115/230 Volt 50/60 Hz
10% 5mA
10%
5A
Yes
Yes
Output Contact
Transfer Contact 250VAC 0.2A at inductive load*
Transfer Contact 250VAC 0.2A at inductive load*
Test Button
Yes
Yes
Withstanding Voltage
1500VAC @ 60Hz for 1 min. between terminal and enclosure
1500VAC @ 60Hz for 1 min. between terminal and enclosure
Surface Color
Munsell 7.5BG4/1.5
Munsell 2.5Y/2
Weight
2.2 lbs.
2.6 lbs.
Power Consumption
1.2VA
1.2VA
Operating Temperature Range
14°F - 122°F
14°F - 122°F
Operating Humidity
85% R.H. or less
85% R.H. or less
Max. Elevation
1,000m
1,000m
Atmosphere
Free of corrosive gas and dust
Free of corrosive gas and dust
SPECIFICATIONS*
FEATURES
TSBSS
TSBSA
Motor Amps
Refer to page D-10
Refer to page D-10
Load Current Range
10 - 130%
10 - 130%
Start Time Setting Range Shock Time Setting Range Input Voltage for Operation Allow. Input Voltage Fluctuation Input Current from C.T. Secondary Meter Fine Tuning Adjustment
0.2 ~ 30 sec. 0.2 ~ 10 sec. 90 ~ 250 VAC
0.2 - 30 sec. 0.2 - 10 sec. 90 ~ 250 VAC
10%
10%
NA NA
NA NA
Output Contact
3A/250 VAC,
3A/250 VAC,
Resistive
Resistive
Test Button
Yes
Yes
Withstanding Voltage
2000VAC, 5mA @ 60Hz for 1 min. between terminal and enclosure
2000VAC, 5mA @ 60Hz for 1 min. between terminal and enclosure
Surface Color
NA
NA
Weight
0.35 lbs.
0.35 lbs.
Power Consumption
2.7VA
2.7VA
Operating Temperature Range
-4°F - 158°F 45 - 85% R.H.
-4°F - 158°F 45 - 85% R.H.
Operating Humidity
Max. Elevation
2,000m
2,000m
Atmosphere
Free of corrosive gas and dust
Free of corrosive gas and dust
SPECIFICATIONS*
FEATURES
TSB151A
TSB152A
Motor Amps
0.25 - 16 amps
17 - 400 amps
Load Current Range
30 - 130% 30 - 130%
30 - 130% 30 - 130%
Alarm Load Current Range Start Time Setting Range Shock Time Setting Range Input Voltage for Operation
0.2 - 20 sec. 0.2 - 3 sec.
0.2 - 20 sec. 0.2 - 3 sec.
115 Volt 50/60 Hz
115 Volt 50/60 Hz
Allow. Input Voltage Fluctuation Input Current from C.T. Secondary Meter Fine Tuning Adjustment
10% 5mA
10%
5A
Yes
Yes
Output Contact
Transfer Contact 250VAC 0.2A at inductive load*
Transfer Contact 250VAC 0.2A at inductive load*
Test Button
Yes
Yes
Withstanding Voltage
1500VAC @ 60Hz for 1 min. between terminal and enclosure
1500VAC @ 60Hz for 1 min. between terminal and enclosure
Surface Color
Munsell 7.5BG4/1.5
Munsell 2.5Y7/2
Weight
2.2 lbs.
2.6 lbs.
Power Consumption
1.2VA
1.2VA
Operating Temperature Range
14°F - 122°F
14°F - 122°F
Operating Humidity
85% R.H. or less
85% R.H. or less
Max. Elevation
1,000m
1,000m
Atmosphere
Free of corrosive gas and dust
Free of corrosive gas and dust
*CAUTION: If the starter coil in the magnetic contactor (MC) of the monitored motor exceeds the Shock Relay output contact’s capacity, an auxiliary relay must be installed to prevent damage to the Shock Relay. The instruction manual included with each Shock Relay details how to add this auxiliary relay if required.